Page 3 - American Power Conversion Legal Disclaimer
American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American Power Conversion Corpora- tion to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development ...
Page 5 - Contents
Contents InRoom SC 60 Hz User Manual i General Information ........................................................ 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 7 - General Information; Overview; Save these instructions
1 InRoom SC 60 Hz User Manual General Information Overview Save these instructions This manual contains important instructions that must be followed during the installation of this equipment. About the InRoom SC Portable Cooling Units InRoom SC cooling units are portable, compact air conditioners de...
Page 8 - Safety symbols that may be used in this manual; Cross-reference symbol used in this manual
InRoom SC 60 Hz User Manual 2 Safety symbols that may be used in this manual Electrical Hazard: Indicates an electrical hazard which, if not avoided, could result in injury or death. Danger: Indicates a hazard which, if not avoided, could result in severe personal injury or substantial damage to pro...
Page 9 - Safety
3 InRoom SC 60 Hz User Manual Safety Electrical Hazard: Connect the equipment to a 3-wire AC outlet (two poles plus a ground). The receptacle must be connected to a dedicated, properly grounded 120 volt 60Hz branch circuit rated for 20 amp main protection (fuses/circuit breaker). Connection to any o...
Page 10 - Storing the Cooling Unit; Cooling Unit Packaging
InRoom SC 60 Hz User Manual 4 Storing the Cooling Unit If the cooling unit will not be installed immediately, replace the packaging to protect from damage and dust. Store the cooling unit indoors in a climate controlled, dry place. Caution: Leaving the cooling unit uncovered and exposed to the eleme...
Page 11 - Inspecting the Cooling Unit; Filing a claim
5 InRoom SC 60 Hz User Manual Inspecting the Cooling Unit Your cooling unit has been tested and inspected before shipment. To ensure that the cooling unit has not been damaged during transit, carefully inspect the cooling unit immediately upon receipt. Verify that all parts ordered were received as ...
Page 12 - Tools Required
InRoom SC 60 Hz User Manual 6 Tools Required Inventory The cooling unit includes the remote control storage bracket, hardware, batteries, the remote control, and the exhaust kit.See “Remote Control” on page 17 for more information. See “Exhaust kit” on page 10 for contents. Phillips head screwdriver...
Page 13 - Component Identification
7 InRoom SC 60 Hz User Manual Component Identification ACPSC2000 and ACPSC3500 Item Description 1 Control panel 2 Vertical air louver 3 Remote control / storage 4 Air filter / upper air intake (evaporator) 5 Air outlet (heat exchanger) 6 Power cord 7 Lower air intake (condenser) 8 Water outlet drain...
Page 14 - Power plug
InRoom SC 60 Hz User Manual 8 Power plug Electrical Hazard: This equipment requires an LCDI plug. Use only the power cord supplied with the equipment. Important safety feature. The plug of the power cord contains a fuse as a safety feature to protect the cooling unit from damage. The fuse in the plu...
Page 15 - Installation; Location; Requirements
9 InRoom SC 60 Hz User Manual Installation Location Requirements When deciding where to locate the cooling unit, consider cooling needs, air flow, and the location of the electrical outlet. The cooling unit can be no more than 2.4 m (8 ft) from the electrical outlet, condenser intake and exhaust acc...
Page 16 - Exhaust Duct Assembly; Exhaust kit
InRoom SC 60 Hz User Manual 10 Exhaust Duct Assembly Dry Mode. Exhaust air must be allowed to return to the room in order for dehumidification to take place. Do not connect the exhaust hose to vent it outside the room. Continuous drainage for the condensate drain pan must be provided or it will fill...
Page 18 - Condensate Drain; Manual draining
InRoom SC 60 Hz User Manual 12 Condensate Drain The InRoom SC utilizes evaporative technology, which eliminates the need for a condensate tank. To manage any excess condensation, a drain pan is located in the bottom of the unit. When the drain pan is full, a light will flash on the display and an al...
Page 19 - Continuous draining
13 InRoom SC 60 Hz User Manual Continuous draining Note: Continuous drainage is recommended when the unit is used in DRY mode. Caution: Condensate draining is done by gravity. Do not run a drain hose to a drain that is located above the drain port of the cooling unit. na3393a
Page 20 - Operation; Control Panel; Function Button Locations
InRoom SC 60 Hz User Manual 14 Operation Control Panel Function Button Locations Item Function Description 1 Power control Turn the cooling unit On and Off 2 Mode selection Three mode control settings: Cool, Dehumidify, and Fan.The settings are adjusted by pressing the Mode Control Button. 3 Remote ...
Page 21 - Display Interface; Display Screen Information
15 InRoom SC 60 Hz User Manual Display Interface Display Screen Information Item Function Description 1 Sleep mode indicator Sleep mode is an undercooling mode that is used during times of non-peak heat. Sleep mode is activated by setting the timer. The set temperature will automatically increase at...
Page 22 - Function Button and Indicator Light Operation
InRoom SC 60 Hz User Manual 16 Function Button and Indicator Light Operation Cooling Mode. In Cool mode the unit attempts to bring the room air temperature down to the set temperature. The fan speed and temperature are adjusted in Cool mode. Note: The room temperature must be higher than the set tem...
Page 23 - Remote Control
17 InRoom SC 60 Hz User Manual Remote Control Caution: 1. Do not drop the remote control. 2. Do not leave the remote control exposed to direct sunlight. Note: 1. To avoid interference, do not use the remote control within one meter (3 ft) of a television or other electrical appliance 2. The remote c...
Page 25 - Maintenance; Clean the exterior; Replace the air filter
19 InRoom SC 60 Hz User Manual Maintenance Electrical Hazard: Before performing maintenance on the cooling unit: 1. Turn the cooling unit off.2. Unplug the cooling unit. Warning: Damage to equipment may occur if: 1. Caustic substances are used to clean the cooling unit. 2. The unit is subjected to e...
Page 26 - Empty the condensate drain pan
InRoom SC 60 Hz User Manual 20 Empty the condensate drain pan If the cooling unit is not equipped with a drain hose allowing the drain pan to drain, the unit will shut down when the drain pan is full. 1. With the power off and the unit unplugged, move the cooling unit to an appropriate place to drai...
Page 27 - Caster replacement
21 InRoom SC 60 Hz User Manual Caster replacement Warning: Tipping the cooling unit can cause damage. 1. Raise the unit levelly at least 406 to 508 mm (16 to 20 in) to access the caster. 2. Remove the two Phillips head screws securing the old caster to the cooling unit. 3. When the old caster is rem...
Page 28 - Troubleshooting
InRoom SC 60 Hz User Manual 22 Troubleshooting Problem Solution Unit does not run Tripped overcurrent protector: Reset the overcurrent protector.If you are attempting to run the cooling unit from the remote control, check that the batteries in the remote control are good.Check that the unit is prope...
Page 29 - Spare Parts List
23 InRoom SC 60 Hz User Manual Spare Parts List Part Number Description 0J-0H-0307 Ceiling exhaust kit 0J-0H-0308 Exhaust duct kit 0J-870-16521 Swivel caster 0J-876-0318 Air filter
Page 30 - Specifications
InRoom SC 60 Hz User Manual 24 Specifications Model APCSC2000 APCSC3500 Net weight (Equipment only) 31 Kg (68 lb) 33 Kg (73 lb) Shipping weight 37 kg (82 lb) 42 kg (92 lb) Dimensions 840 x 685 x 370 mm (33.07 H x 14.57 D x 17.72 W in) Voltage/Frequency 120VAC - 60 Hz 120VAC - 60 Hz Power input 1170 ...
Page 32 - APC Worldwide Customer Support
10/2010 990-3862A-001 APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com (Corporate Head...