990-3051C-001

12/2009

Installation

Modular Rack-Mount Power

Distribution Unit

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions for the modular rack-mount
Power Distribution Unit (PDU) that should be followed during
installation and maintenance of this unit.

Handling Safety

Heavy:

To prevent back injury, two or more people are

required to install the PDU in a rack.

Electrical Safety

Warning:

To reduce risk of electric shock or injury to

persons, disconnect all sources of power before servicing.

Note:

Install the unit in accordance with the National and

Canadian Electrical Codes, and if applicable, local codes.

Note:

To prevent arcing when removing an APC

Power Distribution Module (PDM) from the PDU,
set all PDMs to

OFF

. Do not remove the modules

under load.

Inventory

How to perform a Total Power Off

1

Set all the APC Power Distribution Modules (PDM) to the

OFF

position.

2

Set the utility/mains circuit breaker to the

OFF

position.

3

If the utility/mains is an UPS, set the UPS and its circuit breaker
supplying this product to the

OFF

position.

4

Disconnect the input conductors from the utility/mains or the UPS.

Installation

How to install the PDU

1

Install the mounting rails in the enclosure by using the screws

provided. The PDU requires a 5U space from the top of the

enclosure.

2

Slide the support tray into the mounting rails and secure it with the

screws provided.

3

Slide the PDU on to the support tray and secure it to the front posts of
the enclosure with the screws provided.

4

Slide the bracket tie-downs onto the guide pins on the side of the
PDU and secure the tie-downs to the back posts of the enclosure with
the screws provided.

Item

Part Number

Quantity

Modular rack-mount PDU 138 KW
200 A 400 V 18 Pole 5U

0G-PDPM138H-5U
and
0G-PDPM72F-5U

1

Literature kit rack-mount PDU

0L 1532

1

Label kit rack-mount PDU

0M-8909

Rail stationary black

870-8197D-001

2

Rail adjustable black

870-8198D-001

2

Tray support chassis rack-mount PDU

870-14067

1

Screw M6x12 phil flat head

803-0608

6

Nut M6 flanged hex

803-2406A

6

Washer M6 black plastic cup

803-0009B

14

Screw M6x16 phillips/slot

803-0616B

14

Nut cage M6 14/16 swg

803-0006A

6

Bracket tie-down rear rack-mount PDU

870-14158

2

Plate blank cover brain PCB

870-14159

1

5 U

pd

x0

24

4a

1

p

dx

02

40

a

2

pd

x0

2

42

a

3

4

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Input cables; Enlarge the knock out hole for larger conduit; Install input cables; Communication cables

2 Input cables Enlarge the knock out hole for larger conduit Note: The cutout on the top (or bottom) cover plate may need to be enlarged depending on the installation requirements. 1 If the conduit size for your installation is too large for the conduit access knock out, the hole must be enlarged. 2...

Page 3 - Specifications; Input conductors

3 Specifications Input conductors This product is rated 200 A. It should be supplied with a circuit breaker with a maximum rating of 200 A. For North America, if supplied by a 200 A circuit breaker, it is recommended that conductors are sized in accordance with Table 3. For countries outside of Nort...

Page 4 - Regulatory Agency Approval; APC Worldwide Customer Support

4 Physical Dimensions, Environment and Compliance Note: APC’s products, similar to most computing products, are designed to operate in an environment from 0 to 40°C. Most data centers will maintain an operating temperature between 0 to 30°C. Conductor Ampacity tables of the National Electrical Code ...