  • Page 2 – RCC/RCE Single Phase Units; INSTALLATION INSTRUCTIONS; WARNING
  • Page 3 – FINAL WIRING; Single-Phase Unit Shown
  • Page 4 – CAUTION; SERVICER’S NOTE
Loading the manual

C o m fo r t. Q u a l i ty . Tru st.

Heating

®

&

Air Conditioning

LOW AMBIENT CONTROL

I

NSTALLATION

I

NSTRUCTIONS

Goodman Company, L.P.

1810 Wilson Parkway • Fayetteville, Tennessee 37334

www.amana-hac.com

LAC01A

Description

The Low Ambient Control LAC01A kit is designed for use with

Amana

®

RCC, RCE single-phase

remote condensing

units, and

Amana

®

RCB, VCA and VCB three-phase

remote condensing units. As shipped, these condensing units

are suitable for operation at outdoor temperatures of

50°F

and above

. Used in conjunction with the LAC01A kit,

these units can be used in

outdoor ambient temperatures

as low as 35°F.

This control operates by stopping the

outdoor fan when the high side pressure becomes too low. The fan will automatically restart when the high side
pressure rises.

CAUTION

To avoid compressor damage and loss of warranty coverage, do NOT install this kit in an
indoor coil system that does not include a thermostatic expansion valve.

This kit includes:
Refrigerant Tee, With Two Valve Cores
Low Ambient Cutout Control
Wire Nut
Low Ambient Label
Installation Instructions
Teflon Seals

Part No. 10664121 Rev. 1
Printed in USA

November 2002

ATTENTION INSTALLING PERSONNEL

As a professional installer you have an
obligation to know the product better than the
customer. This includes all safety precautions
and related items.
Prior to actual installation, thoroughly familiarize
yourself with this Instruction Manual. Pay
special attention to all safety warnings. Often
during installation or repair it is possible to place
yourself in a position which is more hazardous
than when the unit is in operation.

Remember, it is your responsibility to install the
product safely and to know it well enough to be
able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter
of thinking before acting. Most dealers have a
list of specific good safety practices...follow
them.
The precautions listed in this Installation Manual
are intended as supplemental to existing
practices. However, if there is a direct conflict
between existing practices and the content of
this manual, the precautions listed here take
precedence.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - RCC/RCE Single Phase Units; INSTALLATION INSTRUCTIONS; WARNING

2 See the outdoor unit Installation Instructions for other “Safe Refrigerant Handling” guidelines. The LAC01A Kit is installed onto the unit discharge line fitting. To install, remove and set aside the control box coverand screws. Carefully swing the control box cover 90° counterclockwise and follow...

Page 3 - FINAL WIRING; Single-Phase Unit Shown

3 1. Disconnect the Violet-20 fan motor lead (not the compressor lead) from the contactor (Terminal T2 onsingle-phase units, Terminal T1 on three-phaseunits). 2. Install the supplied straight female terminal wire (blue), onto the contactor (Terminal T2 on single-phase units, Terminal T1 on three pha...

Page 4 - CAUTION; SERVICER’S NOTE

4 ® is a trademark of Maytag Worldwide N.V. and is used under license toGoodman Company, L.P. All rights reserved. CAUTION Avoid servicing the low ambient control while the unit is operating. The rotating fan bladescould cause serious injury. If measurement of the high side pressure is required, use...