- INSTRUCTIONS -
The NDR-nRS Lamp Memory System is designed for use with the NE-NVP-RA Rescue Assistance sub stations.
The NE-NVP-RA provides communication and call status indication for applications with ADA requirements for
Areas of Rescue Assistance. The NE-NVP-RA features Braille signage, a large red call button, and "call placed"
and "help coming" LED indicators. The sub station flush mounts into a 3-gang masonry-type box, or surface
mounts in the SBX-NVP. Tamper proof screws are provided, along with a wrench for installation. Remote lamps
can be added for better visibility of a station's status. The NDR-nRS master station is equipped with a door
release button and a reset button to reset calls at the master station. The NDR-nRS has outputs to activate an
external device, such as a CCTV camera when the associated sub station is selected, or selectively controlling
the corresponding door strike or maglock.
WIRING DIAGRAM: SYSTEM USED FOR CCTV CAMERA CALL-UP
NDR-RS
NDR Lamp Memory Master Station with External Control Capability for Rescue Assitance
NDR-10RS
NDR-20RS
NDR-30RS
NDR-40RS
NDR-10ARS NDR-20ARS NDR-30ARS NDR-40ARS
Individual Components for System:
NDR-
nRS
Master station with selective contact output capability (10, 20, 30, 40)
NDR-
nARS
Master station w/hndst andcontact output capability (10, 20, 30, 40)
ND-20AS
20-call Add-on Selector with selective output capability (Require PS-2410A)
ND-40AS
40-call Add-on Selector with selective output capability (Requires PS-24E)
RY-PA
Relay for selective output (1 per station requiring external contact)
PS-2410A24V DC, 1A Power Supply for 10-20 station systems
PS-24E
24V DC, 2A Power Supply for 30-40 station systems
NE-NVP-RA
Vandal proof sub station with call status indicators and braille signage
IMPORTANT:
1. RY-PA must be used for each additional contact
to isolate AC voltage from the intercom circuit.
2. Extra contact connections and L are on separate
terminal block. NDR-30/40RS have two terminal blocks.
Special
Order
Products
NDR-20RS
+
-
PS-2410A
Pg. 1
1
L
2
RY-PA
#1
BLK
H
RY-PA
#2
NDR-RS Master
RY-PA
#1
RY-PA
#2
BLK
BLK
BLK
YEL
Momentary closure #1
YEL
Constant closure #1
YEL
Momentary
closure #2
YEL
Constant
closure #2
Equipment for each station that requires
both a constant closure and momentary
closure when a channel is selected:
2 RY-PA relays
1 Diode (1N4001)
DUAL FUNCTIONS FROM EACH CHANNEL:
Terminal Block
NDR-RS TERMINAL DEFINITIONS:
+
Positive 24V DC
-
Negative
1~40
Station number
E
Common communication
S
Sends "call placed" tone to sub
H
Resets call signals at sub when RESET
button is pressed.
1
2
3
~
20 L
BLK
YEL
External
Terminal Block
Normally Open contacts remain
closed as long as master has sub
station selected.
Closure for Station #2
Closure for Station #3
BLK
YEL
BLK
YEL
Closure for Station #1
RY-PA
#3
RY-PA
#2
RY-PA
#1
NE-NVP-RA
Red
Blu
Pur
Blk
Yel
Org
Green
jumper
NE-NVP-RA
Red
Blu
Pur
Blk
Yel
Org
Green
jumper
NE-NVP-RA
Red
Blu
Pur
Blk
Yel
Org
Green
jumper
Leave green
jumper intact
1
2
3
~
20
E
S
H
+
-
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.