Aiphone ND-20AS - Manual

Aiphone ND-20AS

Aiphone ND-20AS – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

- INSTRUCTIONS -

The NDR-nRS Lamp Memory System is designed for use with the NE-NVP-RA Rescue Assistance sub stations.
The NE-NVP-RA provides communication and call status indication for applications with ADA requirements for
Areas of Rescue Assistance. The NE-NVP-RA features Braille signage, a large red call button, and "call placed"
and "help coming" LED indicators. The sub station flush mounts into a 3-gang masonry-type box, or surface
mounts in the SBX-NVP. Tamper proof screws are provided, along with a wrench for installation. Remote lamps
can be added for better visibility of a station's status. The NDR-nRS master station is equipped with a door
release button and a reset button to reset calls at the master station. The NDR-nRS has outputs to activate an
external device, such as a CCTV camera when the associated sub station is selected, or selectively controlling
the corresponding door strike or maglock.

WIRING DIAGRAM: SYSTEM USED FOR CCTV CAMERA CALL-UP

NDR-RS

NDR Lamp Memory Master Station with External Control Capability for Rescue Assitance

NDR-10RS

NDR-20RS

NDR-30RS

NDR-40RS

NDR-10ARS NDR-20ARS NDR-30ARS NDR-40ARS

Individual Components for System:

NDR-

nRS

Master station with selective contact output capability (10, 20, 30, 40)

NDR-

nARS

Master station w/hndst andcontact output capability (10, 20, 30, 40)

ND-20AS

20-call Add-on Selector with selective output capability (Require PS-2410A)

ND-40AS

40-call Add-on Selector with selective output capability (Requires PS-24E)

RY-PA

Relay for selective output (1 per station requiring external contact)

PS-2410A24V DC, 1A Power Supply for 10-20 station systems
PS-24E

24V DC, 2A Power Supply for 30-40 station systems

NE-NVP-RA

Vandal proof sub station with call status indicators and braille signage

IMPORTANT:

1. RY-PA must be used for each additional contact

to isolate AC voltage from the intercom circuit.

2. Extra contact connections and L are on separate

terminal block. NDR-30/40RS have two terminal blocks.

Special
Order
Products

NDR-20RS

+

-

PS-2410A

Pg. 1

1

L

2

RY-PA

#1

BLK

H

RY-PA

#2

NDR-RS Master

RY-PA

#1

RY-PA

#2

BLK

BLK

BLK

YEL

Momentary closure #1

YEL

Constant closure #1

YEL

Momentary
closure #2

YEL

Constant
closure #2

Equipment for each station that requires
both a constant closure and momentary
closure when a channel is selected:
2 RY-PA relays
1 Diode (1N4001)

DUAL FUNCTIONS FROM EACH CHANNEL:

Terminal Block

NDR-RS TERMINAL DEFINITIONS:

+

Positive 24V DC

-

Negative

1~40

Station number

E

Common communication

S

Sends "call placed" tone to sub

H

Resets call signals at sub when RESET
button is pressed.

1

2

3
~
20 L

BLK

YEL

External

Terminal Block

Normally Open contacts remain
closed as long as master has sub
station selected.

Closure for Station #2

Closure for Station #3

BLK

YEL

BLK

YEL

Closure for Station #1

RY-PA

#3

RY-PA

#2

RY-PA

#1

NE-NVP-RA

Red

Blu

Pur

Blk

Yel

Org

Green

jumper

NE-NVP-RA

Red

Blu

Pur

Blk

Yel

Org

Green

jumper

NE-NVP-RA

Red

Blu

Pur

Blk

Yel

Org

Green

jumper

Leave green

jumper intact

1
2
3

~

20

E
S

H

+

-

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Aiphone Models

All Aiphone Other