Page 2 - ii; Recommendations for Proper Protection; Recommendations For Smoke And Heat Detectors; UL
ii Recommendations for Proper Protection The Following Recommendations For The Location Of Fire And Burglary Detection Devices Help ProvideProper Coverage For The Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subs...
Page 3 - iii
iii In addition, we recommend that radio backup be used in a security system so that alarm signals canstill be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarmsignals are normally sent over the phone lines, if connected to an alarm monitoring station...
Page 4 - iv; Table of Contents
iv Table of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • RECOMMENDATIONS FOR PROPER PROTECTION .................................................................. ii HOW TO USE THIS MANUAL .......................................................
Page 8 - THE LIMITATIONS OF THIS ALARM SYSTEM
Table of Contents viii To Add an RF Key to an Existing User .......................................................................... 27-6 To DELETE a Master, Manager or Operator Code ....................................................... 27-6 To EXIT the User Edit Mode ..............................
Page 9 - ix; List of Figures
ix List of Figures • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 4-1. Installing the Lock......................................................................................................................... 4-1 4-2.. Cabinet Attack Resistance Con...
Page 10 - How To Use This Manual; A general description of the entire system
x How To Use This Manual This manual is written to accommodate both the new and the experienced installer ofADEMCO products. The information contained in this manual is presented in the followingorder. • A general description of the entire system • The wiring and physical setup of the hardware • Pro...
Page 11 - xi; Conventions Used in This Manual; INSTALLER CODE
xi Conventions Used in This Manual Before you begin using this manual, it is important that you understand the meaning of thefollowing symbols (icons). NOTES AND WARNINGS: UL A UL note includes specific information that must be followed if you are installing this system fora UL Listed application. A...
Page 12 - VISTA-100 Installation Instructions; S E C T I O N 1; General Description; In This Section; General Overview; The major system features are outlined below.; Basic Hardwired Zones
VISTA-100 Installation Instructions 1-xii S E C T I O N 1 General Description • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Overview ♦ System Features • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •...
Page 13 - Section 1 - General Description; Supervisory Zones
Section 1 - General Description 1-xiii • Individually assignable to bell outputs and/or aux. relay UL Wireless devices are not permitted in UL Commercial Burglary installations. UL Listing of the5808 Smoke Detector for Commercial Fire installations is pending. For specific information regarding the ...
Page 14 - User Codes
VISTA-100 Installation Instructions 1-xiv • Certain system options are selectable for each partition, such as Entry/Exit Delay and subscriber account number User Codes Accommodates 128 user codes, all of which can operate any or all partitions. The followingcharacteristics must be assigned to each u...
Page 15 - Auxiliary Relay; Access Control; Optional 24-Volt Power Supply
Section 1 - General Description 1-xv Auxiliary Relay Provides a built-in Form C relay which can be used for one of the following purposes: • Alarm activation • Trouble/supervisory activation • 4-wire smoke detector reset • Battery-saving feature (disconnects power from noncritical loads 4 hours afte...
Page 18 - S E C T I O N 2; Planning a Partitioned System; Theory of Partitioning
2-1 S E C T I O N 2 Planning a Partitioned System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Theory of Partitioning ♦ Setting Up a Partitioned System ♦ Common Lobby Logic ♦ Master Keypad Setup and Operation • • • • • • • • • • • ...
Page 19 - Common Lobby Logic
VISTA-100 Installation Instructions 2-2 (multiple access) can "log on" to one partition from another partition's keypad, providedthat program field 2*18: ENABLE GOTO is enabled for each partition to which the userwill log on from another. You can select a partition as a "common lobby"...
Page 20 - Section 2 - Planning a Partitioned System; Affects Lobby; MAIN ENTRANCE; COMMON LOBBY; Office 1
Section 2 - Planning a Partitioned System 2-3 You cannot program a partition to "arm" the lobby unless you first program it to "affect" the lobby.Enable field 1*18 before you enable field 1*19. The following chart sums up how the common lobby partition will operate, depending on theo...
Page 21 - Arming/Disarming Remotely
VISTA-100 Installation Instructions 2-4 Sequence #2: Office 1 Office 2 Lobby Action User #2: (Armed) Disarms Disarms User #1: Disarms (Disarmed) (No change) User #2: (Disarmed) Arms No Change User #1: Arms (Armed) No Change Notice that in Sequence #1, because Office #2 was the last to arm, the lobby...
Page 22 - Master Keypad Setup and Operation
Section 2 - Planning a Partitioned System 2-5 Master Keypad Setup and Operation Although this system has 8 actual partitions, it provides an extra partition strictly for thepurpose of assigning keypads as "Master" keypads for the system. Any keypad you assign to Partition 9 in #93 Device Pro...
Page 24 - S E C T I O N 3; False Alarm Reduction Features; General Information
3-1 S E C T I O N 3 False Alarm Reduction Features • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ Exit Error Logic and Related Reports ♦ Recent Close Report ♦ Exit Delay Reset ♦ Cross-Zoning ♦ Call Waiting Defea...
Page 25 - Recent Close Report; Cross Zoning; • Both must protect the same area; Conditions That Affect Cross-Zone Operation
VISTA-100 Installation Instructions 3-2 • Exit Error by Zone (this is sent as a regular alarm if you are using ADEMCO High Speed format) • Bypass reports Recent Close Report The Recent Close Report notifies the central station that an alarm has occurred within 5minutes of arming. You can program thi...
Page 26 - Call Waiting Defeat Logic
Section 3 - False Alarm Reduction Features 3-3 • If an entry/exit zone is paired with an interior follower zone, be sure to enter theentry/exit zone as the first zone of the pair. This will ensure that the entry delay time isstarted before the follower zone is processed. • If a relay is programmed t...
Page 28 - S E C T I O N 4; Installing The Control; Insert the key into the lock. Position the lock
4-1 S E C T I O N 4 Installing The Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Mounting the Control Cabinet ♦ Installing the Cabinet Lock ♦ Grade A Mercantile Premises Listing ♦ Grade A Mercantile Safe and Vault Listing ♦ ...
Page 29 - Grade A Mercantile Premises Listing; indicated in the diagram below.; Figure 4-2. Cabinet Attack Resistance Considerations; Grade A Mercantile Safe and Vault Listing
VISTA-100 Installation Instructions 4-2 UL For UL installations which are intended to provide certificated burglary service, refer to thespecial requirements and the Cabinet Attack Resistance Considerations diagram below. Grade A Mercantile Premises Listing For a Grade A Mercantile Premises listing,...
Page 30 - Section 4 - Installing The Control; Installing the Control's Circuit Board; with the accompanying screws.; Connecting the AC Transformer and Battery
Section 4 - Installing The Control 4-3 Installing the Control's Circuit Board To install the control’s circuit board, take the following steps and refer to the diagram belowwhen mounting the PC board: 1. Hang the three mounting clips on the raised cabinet tabs. Make sure the clip orientation is exac...
Page 31 - Panel Earth Ground Connections; To ground the panel, take the following steps:
VISTA-100 Installation Instructions 4-4 Panel Earth Ground Connections To ground the panel, take the following steps: 1. Connect the earth ground post inside the 1451 enclosure to a good earth ground (use grounding methods specified in the National Electric Code). Use a green nut (supplied) to secur...
Page 32 - S E C T I O N 5; Installing The Keypads; You may use the following keypads with the VISTA-100:; Wiring to the Keypads; To wire the keypads, take the following steps:; Wire Run Length Table
5-1 S E C T I O N 5 Installing The Keypads • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Keypads That May Be Used ♦ Wiring to the Keypads ♦ Using a Supplementary Power Supply to Power Additional Keypads ♦ Mounting the Keypads ♦ Addr...
Page 33 - Using a Supplementary Power Supply to Power Additional Keypads
VISTA-100 Installation Instructions 5-2 • The length of all wire runs combined must not exceed 2000 feet when unshielded quadconductor cable is used (1000 feet if unshielded cable is run in conduit or if shielded cableis used). • If more than one keypad is wired to a run, the maximum lengths above m...
Page 34 - Mounting the Keypads
Section 5 - Installing The Keypads 5-3 Figure 5-2. Using a Supplementary Power Supply for Keypads Mounting the Keypads Mount the keypads at a height that is convenient for the user. Refer to the instructionsprovided with the keypad for mounting procedure. You can either surface mount or flush mount ...
Page 35 - Programming Remote Keypads
VISTA-100 Installation Instructions 5-4 5. When the proper “READY” message is displayed on the keypad(s) addressed at 00, 01, 02, and 03, the system is functioning properly. Do not remove the EOL resistors until you are ready to make connections to the hard-wired zones, to allow for testing later in...
Page 36 - S E C T I O N 6; supervision is required for fire and UL Burglary installations.); Wiring Burglary and Panic Devices to Zones 1-8; connected across the loop wires at the last device.
6-1 S E C T I O N 6 Basic Hardwired Zones 001-008 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Common Characteristics of Hardwired Zones 1-8 ♦ Wiring Burglary and Panic Devices to Zones 1-8 ♦ Wiring 2-Wire Smoke Detectors to Zones ...
Page 37 - Wiring 2-Wire Smoke Detectors to Zones 1 and 2
VISTA-100 Installation Instructions 6-2 Wiring 2-Wire Smoke Detectors to Zones 1 and 2 Zones 1 and 2 have the added capability of supporting 2-wire smoke detectors. Each zoneprovides enough standby current (2mA) to power up to 16 of the smoke detectors listedbelow. Each zone provides only enough ala...
Page 38 - Compatible 2-Wire Smoke Detectors; DETECTOR TYPE; Wiring 4-Wire Smoke Detectors to Zones 1-8
Section 6 - Basic Hardwired Zones 001-008 6-3 Compatible 2-Wire Smoke Detectors You may use up to sixteen 2-wire smoke detectors each on zones 1 and 2. The detectors youcan use are listed in the table below. DETECTOR TYPE DEVICE MODEL # Photoelectric, direct wire System Sensor 2400 Photoelectric w/h...
Page 39 - Compatible 4-Wire Smoke Detectors; Photoelectric, direct wire; Fire Alarm Verification for Smoke Detectors
VISTA-100 Installation Instructions 6-4 Figure 6-2. 4-Wire Smoke Detector Connections (Zones 1-8) 2. Connect detectors (including heat detectors, if used) across terminals of the zone you have selected. All detectors must be wired in parallel. Remove the 2000-ohm EOLresistor if one is connected acro...
Page 40 - Wiring 2-Wire Latching Glassbreak Detectors to Zone 8; Figure 6-3. Wiring Latching Glassbreak Detectors to Zone 8; Compatible Glassbreak Detectors; Use detectors that meet the following ratings:
Section 6 - Basic Hardwired Zones 001-008 6-5 When you set it in this manner, the zone will trigger a trouble when the panel is disarmedand an alarm when the panel is armed, when the zone senses either an open or a short, orwhen an earth ground fault caused by drilling through the AB12 housing is de...
Page 41 - Programming and Checkout of Hardwired Zones
VISTA-100 Installation Instructions 6-6 Programming and Checkout of Hardwired Zones You must program each zone in order for it to become operational. To program the zones,refer to the procedures for zone programming in Section 22: #93 Menu Mode Programming.Additionally, after all hardwired zones are...
Page 42 - S E C T I O N 7; -Wire Polling Loop Expansion; Refer to the list of compatible devices at the end of this section.; Common Characteristics of Polling Loop Zones; Polling loop zones have the following characteristics:; Wiring/Addressing RPM Devices
7-1 S E C T I O N 7 2-Wire Polling Loop Expansion (Zones 9 - 87) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Polling Loop Overview ♦ Common Characteristics of Polling Loop Zones ♦ Wiring/Addressing RPM Devices ♦ Polling Loop Super...
Page 43 - Maximum Polling Loop Wire Runs
VISTA-100 Installation Instructions 7-2 number or group is determined by the setting of DIP switches. Other devices have a built-inunique serial number which must be programmed into the control as its zone number. Toset up the polling loop, take the following steps: 1. Run wires to each device on th...
Page 44 - Section 7 - 2-Wire Polling Loop Expansion; DO NOT use the 4197 Polling Loop Extender Module with the VISTA-100.
Section 7 - 2-Wire Polling Loop Expansion 7-3 Figure 7-1. Polling Loop Connections The 4297 Polling Loop Extender may be used to provide additional polling loop current, toextend the polling loop wire run length, and/or to provide individual electrically isolatedpolling loops. Refer to Figures 7-2a ...
Page 46 - Polling Loop Supervision
Section 7 - 2-Wire Polling Loop Expansion 7-5 Polling Loop Supervision A short on the polling loop is indicated by a trouble on its supervisory zone, and reports as atrouble condition only. Therefore, if you want an audible trouble alarm, assign the pollingloop to zone type 5 or 19. If a device on t...
Page 47 - Models 7500 and 9500 Glassbreak Detectors are not UL Listed.
VISTA-100 Installation Instructions 7-6 Compatible Polling Loop Devices (cont’d) 4275 Dual PIR • Dual-element PIR with built-in RPM (connects directly to the polling loop). • DIP switch-programmable.• Includes mirrors for both wide-angle and curtain/long-range applications and can usethe 1875PA Pet ...
Page 48 - S E C T I O N 8; Wireless Zone Expansion; Individually assignable to one of 8 partitions; Wireless Systems Available; Receiver; up to 4
8-1 S E C T I O N 8 Wireless Zone Expansion • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Common Characteristics of Wireless Zones ♦ Wireless Systems Available ♦ RF System Operation and Supervision ♦ RF System Installation Advisorie...
Page 49 - up to 8; RF System Operation and Supervision; redundant protection.; RF System Installation Advisories
VISTA-100 Installation Instructions 8-2 5800 Series Receiver Zones 5881L up to 8 5881M up to 16 5881H up to 87 5881EH up to 87 (use with UL864 installations) In Canada, 5800 systems must use 5882 Series receivers: 5882L/5882H. Information in thismanual relative to the 5881 receivers applies as well ...
Page 51 - Installing the 5800TM Module; For additional information, refer to the 5800TM’s instructions.; Programming the RF Receiver
VISTA-100 Installation Instructions 8-4 Installing the 5800TM Module You will need to install this module only if you are using one or more 5827BD Wireless Bi-directional keypads. You must locate the 5800TM next to the 4281 or 5881 Receiver (between one and two feetfrom the receiver’s antennas), and...
Page 52 - Section 8 - Wireless Zone Expansion; 700 Series Transmitter Setup; Transmitter Supervision; OFF to clear its memory of the “Low Battery” signal.; Installing the Transmitters; To install RF transmitters, take the following steps:; Wireless Zone Assignments for 5700 Series Transmitters
Section 8 - Wireless Zone Expansion 8-5 5700 Series Transmitter Setup Each 5700 Series transmitter has DIP switches to set both the transmitter’s zone number(Transmitter ID) and the system House ID. The House ID will be the same for alltransmitters, and must match the House ID programmed into the sy...
Page 53 - Zone Type
VISTA-100 Installation Instructions 8-6 Zone Type Trans/Zone # Entry/Exit Burglary 1 through 47 * Perimeter Burglary 1 through 47 * Interior Burglary 1 through 47 *32 through 47 * (5775) Fire 48 through 63 *48 through 55 ** (5706) 24-Hour Panic (silent or audible) 48 through 63*62 or 63 *** (5701) D...
Page 54 - Compatible 5700 Series Transmitters (cont’d); 800 Series Transmitter Setup
Section 8 - Wireless Zone Expansion 8-7 Compatible 5700 Series Transmitters (cont’d) Model Product Zone No. Description 5775 PIR Detector 32-47 • Dual-element passive infrared detector with built-in selectablepulse count.Note: There is a 3-minute lockoutbetween fault transmissions toconserve battery...
Page 55 - UR or RF
VISTA-100 Installation Instructions 8-8 The supervision for a particular transmitter that may be carried off the premises (5801,5802MN) can be turned off by programming it as a “UR” (Unsupervised RF) type, asdescribed later in this section. 5800 Series transmitters have built-in tamper protection, a...
Page 56 - Compatible 5800 Series Transmitters (cont’d)
Section 8 - Wireless Zone Expansion 8-9 Compatible 5800 Series Transmitters (cont’d) Model Product Program AsInput Type Description 5802 5802CP Pendant (PersonalEmergencyTransmitter) Belt Clip (PersonalEmergencyTransmitter) BR Only • Has a single pushbutton.• Usually programmed for response type of ...
Page 57 - Programming and Checkout of Wireless Zones
VISTA-100 Installation Instructions 8-10 Compatible 5800 Series Transmitters (cont’d) Model Product Program AsInput Type Description 5827 Wireless Keypad House ID • Can be used to turn the burglary protection on and off. • Features the same built-in panic functions as wired keypads. • The keypad is ...
Page 58 - S E C T I O N 9; Relay Outputs; Relay Basics; To wire the 4204 or 4204CF Relay Module, take the following steps:
8-1 S E C T I O N 9 Relay Outputs • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Relay Basics ♦ Wiring the 4204 and 4204CF Relay Modules ♦ Programming Relay Modules and Output Devices • • • • • • • • • • • • • • • • • • • • • • • • •...
Page 60 - Section 9-Relay Outputs; Programming Relay Modules and Output Devices
Section 9-Relay Outputs 9-3 Figure 9-1b: 4204CF Relay Module 3. When you are mounting them remotely, homerun each module back to the control. The table below shows the maximum wire run lengths from the control to each 4204. Refer tothe instructions provided with the 4204CF for its maximum permissibl...
Page 62 - S E C T I O N 1 0; The 4285/4286 VIP Module offers the following features:; Mounting the VIP Module
10-1 S E C T I O N 1 0 4285/4286 VIP Module • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ Mounting the VIP Module ♦ Wiring the VIP Module ♦ Programming the VIP Module • • • • • • • • • • • • • • • • • • • • • •...
Page 63 - Wiring the VIP Module; Terminal Block Connections
VISTA-100 Installation Instructions 10-2 To mount the VIP Module, take the following steps: 1. When the VIP Module is mounted inside the control cabinet, attach it to the cabinet's interior surface with 2-faced adhesive tape. You may leave the Module's cover off if theModule is mounted within the ca...
Page 64 - Programming the VIP Module
Section 10-4285 VIP Module 10-3 ANSWERING MACHINE SPEAKER VOLUMEADJUSTABLE ON4286 ONLY ▲ ▲ 4285/4286 PHONE MODULE 1 2345 6 7 YELLOW: TO DATA OUT (term. 14)NO CONNECTIONRED: TO AUX (+) (term. 11) BLACK: TO AUX. GROUND (–) (term. 12) GREEN: TO DATA IN (term. 13) CONNECTORWITH FLYINGLEADS TO CONTROLPAN...
Page 66 - S E C T I O N 1 1
11-1 S E C T I O N 1 1 Audio Alarm Verification (AAV) Unit • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ AAV Module Operation ♦ Audio Alarm Verification Module Connections ♦ Programming Audio Alarm Verification...
Page 67 - Audio Alarm Verification Module Connections; address, temporarily apply power to the system.
VISTA-100 Installation Instructions 11-2 messages triggered during ongoing conversation will be held until either the AAV modulesignals that it is inactive, or the 15-minute timeout occurs. The AAV module is triggered by the use of a 4204 relay as shown in the Relay Triggerdiagram (Figure 11-1). You...
Page 68 - Section 11 – Audio Alarm Verification (AAV) Unit; Figure 11-1. Audio Alarm Verification Module Connections
Section 11 – Audio Alarm Verification (AAV) Unit 11-3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ▲ ON MODEL EAGLE SECURITY 1241 REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE PREMISESANSWERINGMACHINE ANDPHONES ANSWERING MACHINE ▲ ▲ INCOMING TELCO LINE V+ GND 1 2 3 RELA...
Page 70 - S E C T I O N 1 2; J2 Trigger Outputs; • Remote keypad sounder
12-1 S E C T I O N 1 2 J2 Trigger Outputs • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ Remote Keypad Sounder Operation and Wiring ♦ Remote Keyswitch Operation and Wiring ♦ 5140LED Indicator Module ♦ Auxiliary ...
Page 71 - Remote Keypad Sounder Operation and Wiring; Figure 12-2. Remote Keypad Sounder Wiring; Remote Keyswitch Operation and Wiring
VISTA-100 Installation Instructions 12-2 Figure 12-1. J2 Pin Assignments and Functions Remote Keypad Sounder Operation and Wiring You can use an optional Amseco PAL 328N Piezo Sounder for installations where you wantto duplicate the sounds produced by the keypad's built-in sounder. The panel will du...
Page 73 - Keyswitch Operation With Alarms Present:
VISTA-100 Installation Instructions 12-4 Keyswitch Operation With Alarms Present: A momentary short across zone 7 will silence alarm bell and keypad sounds, and will disarmthe system if it was armed. The keyswitch LEDs provide a memory of alarm indication (seetable below). A subsequent short across ...
Page 74 - Section 12 – J2 Trigger Outputs; Auxiliary Alarm Signaling Equipment
Section 12 – J2 Trigger Outputs 12-5 If you use this feature, set program field 3*20 to 2, and connect the 5140LED module toJ2/OUT 1, 3, 4, 5, as shown in Figure 12-4. The module is designed to be mounted into astandard single-gang electrical box and installed as follows: 1. Pull the wires from the ...
Page 75 - Figure 12-5a. Connections to 7720 Long Range Radio
VISTA-100 Installation Instructions 12-6 The fire and burglary/audible panic alarm triggers remain HIGH until a [User Code] + OFFis entered in all enabled partition(s) which display these conditions. The silent panic/duresstrigger works the same way, except that it is momentary when initiated by dur...
Page 76 - Figure 12-5c. Connections to 7920SE Long Range Radio
4.7K (NOTE) ZONE 1 TB2 1 2 3 4 5 6 7 8 9 10 TB1 1 2 3 4 5 6 7 8 9 10 CONNECT TO POLLING LOOP GROUND SCREW ZONE 2 ZONE 3 ZONE 4 ZONE 5 FAULT CABINET GROUND EAR TH GROUND SEE 7920SE INST . INSTR. FOR INSTRUCTIONS ON POWERING GROUND FIRE ALARM SILENT PANIC ALARM FIRE SUPERVISORY TROUBLE BURGLARY/AUDIBL...
Page 77 - Event Log Printer Connections; If earth ground fault sensing is enabled:; Direct Wire Downloading
VISTA-100 Installation Instructions 12-8 Event Log Printer Connections The VISTA-100's event log can be printed on a local serial printer. If you use the event log,program field 3*19 to 1. This setting overrides the functions selected for INPUT 1 and OUT 2 made in field 3*20. Connect a UL EDP Listed...
Page 79 - S E C T I O N 1 3; External Sounders; Bell Circuit Supervision; To supervise bell circuits, take the following steps:; each bell output you want supervised.
13-1 S E C T I O N 1 3 External Sounders • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ Bell Circuit Supervision ♦ Programming the Bell Outputs ♦ Wiring ♦ Compatible Alarm Indicating Devices • • • • • • • • • • ...
Page 80 - Programming the Bell Outputs; Model
VISTA-100 Installation Instructions 13-2 To unsupervise bell circuits, take the following steps: 1. Cut the white jumpers W1 (for Bell 1) and/or W4 (for Bell 2) on the main PCB.2. Program zones 970 (Bell 1) and 971 (Bell 2) for a response type of 00 to disable supervision (#93 Zone Programming Mode)...
Page 81 - Section 13 - External Sounders; Strobe; Figure 13-1. External Sounder Connections
Section 13 - External Sounders 13-3 Model Description System Sensor MASS121575 ADA Horn/Strobe System Sensor MA/SS-12 Horn/Strobe Wheelock LS1-12-VFR Strobe Wheelock MS1-12-VFR Strobe Wheelock MT-12-LS-VFR Horn/Strobe Wheelock MT4-12-LS-VFR Horn/Strobe Wheelock MT-12-MS-VFR Horn/Strobe Wheelock MT4-...
Page 82 - S E C T I O N 1 4; Relay Functions; These functions are described below.; Figure 14-1. Auxiliary Relay Used as Unsupervised Bell Output
14-1 S E C T I O N 1 4 Auxiliary Relay • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Relay Functions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Relay Functions The VISTA-100 provi...
Page 84 - Section 14- Auxiliary Relay
Page 85 - S E C T I O N 1 5; Dialer Outputs; Dialer Outputs Available; Telephone Line Supervision; DO NOT connect both outputs to the same telephone company line.
15-1 S E C T I O N 1 5 Dialer Outputs • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Dialer Outputs Available ♦ Telephone Line Connections ♦ Telephone Line Supervision ♦ Dialer Operation • • • • • • • • • • • • • • • • • • • • • • • ...
Page 86 - Dialer Operation; The VISTA-100 will transmit reports in the following order:
VISTA-100 Installation Instructions 15-2 • To prevent the risk of shock, disconnect phone lines at telco jacks before servicing the panel. • If the communicator is connected to a telephone line inside a PABX, be sure the PABX has abackup power supply that can support the PABX for 24 hours (central s...
Page 87 - Section 15- Dialer Outputs
Page 88 - S E C T I O N 1 6; Event Log Options; To enable event log printing, take the following steps:
16-1 S E C T I O N 1 6 Event Log Options • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ Event Log Printer Connections ♦ Programming Event Log Options ♦ Event Logging Procedures • • • • • • • • • • • • • • • • • ...
Page 89 - Figure 16-1. Event Log Printer Connections; cannot be lengthened to mount the module in a remote location.; Programming Event Log Options; To program event log options, take the following steps:
VISTA-100 Installation Instructions 16-2 1 2 3 4 5 6 7 8 9 J2 CONNECTOR 4142TR CABLE 8 7 6 5 4 3 2 1 4100SM + PWR - (GND) RXD not used not used not used not used DTR RED BLUE WHITE TO AUX PWR 1 OUTPUT 10 FT. CABLE SUPPLIED WITH 4100SM USE GENDER CHANGERSUPPLIED WITH 4100SMIF PRINTER HAS DB25MALE CON...
Page 90 - Section 16- Event Log Options; Event Logging Procedures
Section 16- Event Log Options 16-5 5. Exit Program Mode by pressing *99. NOTE: For more information about actual programming procedures, see Section 18: TheMechanics of Programming. Event Logging Procedures In order for proper time and date stamping to occur, you must set the system's real-time cloc...
Page 91 - Display shows all test events.; SCREEN DEFINITIONS; RECENT
VISTA-100 Installation Instructions 16-4 ALL EVENT LOGTYPE CCC UUU Display shows all categories of events in chronological orderfrom most recent to oldest. TEST EVENT LOGTYPE CCC UUU Display shows all test events. To display the events in a particular category, press 8 at the desired category screen...
Page 93 - S E C T I O N 1 7; Final Power-Up Procedure; Connecting the AC Transformer; Remove the front cover of the enclosure.
17-1 S E C T I O N 1 7 Final Power-Up Procedure • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Connecting the AC Transformer ♦ Backup Power Calculations ♦ Connecting the Backup Battery to the Control • • • • • • • • • • • • • • • • •...
Page 94 - Connecting the Panel to Earth Ground; to determine the total current drawn from the polling loop.
VISTA-100 Installation Instructions 17-2 5. Replace the front cover of the enclosure and fasten it with the screws supplied. A few seconds after power is applied to the control, the keypad should display"DISARMED...READY TO ARM." If there is no keypad display, verify that the 1451Transformer...
Page 95 - Section 17 – Final Power-Up; Connecting the Backup Battery to the Control; Figure 17-1. Connecting the Backup Batteries to the Control
Section 17 – Final Power-Up 17-3 Select one of the batteries (listed in the Battery Selection Table later in this section)which has a capacity greater than or equal to the battery capacity you calculated. Connecting the Backup Battery to the Control If you are not using the PS24, connect the battery...
Page 96 - Total Control Panel Load Worksheets; Enter devices used on; Enter devices connected
VISTA-100 Installation Instructions 17-4 Total Control Panel Load Worksheets To calculate the total current for the Aux. Power 1, Aux. Power 2, Bell 1 and Bell 2 outputs and polling loopcurrent, multiply each device's standby and/or alarm current by the number of units used. 1. Enter devices used on...
Page 98 - BATTERY SELECTION TABLE
VISTA-100 Installation Instructions 17-6 Capacity Formula Calc Value StandbyCapacity Total standby load x 24 or 60 hours x 1.1contingency factor (use total standby load from theprevious worksheet) Alarm Capacity Total alarm load x 0.083 hours (5 minutes) or 0.250hours (15 minutes)(use total alarm lo...
Page 100 - S E C T I O N 1 8; The Mechanics Of Programming; then either make the required entry in the new field, or press; System and Communication Defaults; 7) enable keypad addresses 00-03 only. You must use a keypad
18-1 S E C T I O N 1 8 The Mechanics Of Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Using Data Field Program Mode ♦ System and Communication Defaults ♦ Entering Data Field Programming Mode ♦ Moving from One Page of Pro...
Page 101 - Entering Data Field Programming Mode
VISTA-100 Installation Instructions 18-2 Entering Data Field Programming Mode Enter Data Field Program Mode using one of these methods: • Press both the ✴ and [#] keys at the same time within 30 seconds after power is applied to the control. • Enter [Installer Code] + 8 + 0 + 0 + 0. You can change t...
Page 102 - Section 18 - The Mechanics of Programming; SUMMARY OF DATA FIELD PROGRAMMING COMMANDS; Programming System-Wide Data Fields; Press; Programming Partition-Specific Data Fields; The system will prompt you for the partition number.
Section 18 - The Mechanics of Programming 18-3 • In either of the above cases, simply re-enter ✴ plus the correct field number. SUMMARY OF DATA FIELD PROGRAMMING COMMANDS ✴ 94 View the next page of fields ✴ 99 View the previous page of fields or exit Programming Mode with no Installer Code lockout ✴...
Page 103 - #93 Menu Mode Programming; #93 Menu Mode Key Commands
VISTA-100 Installation Instructions 18-4 you have finished entering the partition-specific fields, enter the number of any globalfield. Repeat Steps 1 and 2 for each partition in the installation. The table below summarizes the steps you take in programming partition-specific fields: PROGRAMMING PAR...
Page 104 - S E C T I O N 1 9; Zone Number Designations; Zone; Traditional hardwired zones; Zone Type Definitions; Type 00: Zone Not Used
19-1 S E C T I O N 1 9 Zone Type Definitions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Zone Number Designations ♦ Zone Type Definitions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • ...
Page 105 - Type 03: Perimeter Burglary
VISTA-100 Installation Instructions 19-2 Type 02: Entry/Exit #2 Burglary This zone type provides a secondary entry delaywhenever the zone is faulted if you arm the panelin the AWAY and STAY modes. When you armthe panel in the INSTANT or MAXIMUM mode,no entry delay is provided. Secondary exit delaybe...
Page 106 - Section 19 - Zone Type Definitions; Type 17: Fire Waterflow
Section 19 - Zone Type Definitions 19-3 response. Initial short detection causes 6-secondsmoke detector power reset. A subsequent shortdetection within 90 seconds of reset causes a firealarm. Type 17: Fire Waterflow An open on this zone causes a trouble response.Shorts that remain present longer tha...
Page 108 - S E C T I O N 2 0; Zone Index/Zone Type Defaults; Zone Index; ZONE NUMBER RANGE
20-1 S E C T I O N 2 0 Zone Index/Zone Type Defaults • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Zone Index ♦ Zone Type Defaults • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Zone ...
Page 109 - Zone Type Defaults
VISTA-100 Installation Instructions 20-2 Zone Type Defaults The following tables detail the zone type defaults for zones on the VISTA-100: Zone # Zone Type 001 09 002 09 003 03 004 03 005 03 006 03 007 03 008 03 Zone # Zone Type 009–087 00 601–616 19 800–831 00 970 00 971 19 972 19 973 19 974 19 Zon...
Page 110 - S E C T I O N 2 1; Data Field Descriptions; *08 TEMPORAL SIREN PULSE; If you program either bell for pulsing (program field 3
21-1 S E C T I O N 2 1 Data Field Descriptions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • The following is a description of all data fields provided by the VISTA-100. If you havefollowed earlier instructions during the installation of the various ...
Page 111 - *15 KEYSWITCH ASSIGNMENT
VISTA-100 Installation Instructions 21-2 *13 BELL 1 TIMEOUT (partition-specific) [04] | This field defines the length of time Bell Output 1 and the keypad's sounder will soundfor all audible alarms (multiply your entry of 01-15 by 2 minutes for the actualduration). For UL Commercial Burglary install...
Page 112 - Section 21 - Data Field Descriptions; You must set this field to 1 for UL installations.; Note that if the previous state was
Section 21 - Data Field Descriptions 21-3 *22 KEYPAD PANIC ENABLES (partition-specific) [001] | | 995 996 999 Enter 1 to enable the appropriate keypad panics used in this partition. Enter 0 if youdo not want to enable keypad panics. *23 MULTIPLE ALARMS (partition-specific) [0] This field determines ...
Page 113 - *30 TOUCHTONE OR ROTARY DIAL; This field is applicable only if the user will use downloading.
VISTA-100 Installation Instructions 21-4 29 QUICK ARM (partition-specific) [0] If you enable Quick Arm, the user can arm the burglary system in AWAY, STAY,INSTANT, or MAXIMUM modes by using the [#] key instead of the User Code. Whenarmed, the system reports a closing as User No. 0 if you enabled Ope...
Page 114 - *36 DOWNLOAD ID NUMBER; 3 to disable the download callback option.; Set this field to 0 for Commercial Fire and UL installations.
Section 21 - Data Field Descriptions 21-5 Enter the downloading phone number, up to 17 digits (the same as in fields *33 and*34). Do not fill unused spaces. *36 DOWNLOAD ID NUMBER | | | | | | | | Enter this number only if the user will use downloading. Make entries as 2-digitnumbers, as follows: 00=...
Page 115 - *44 RING DETECTION COUNT
VISTA-100 Installation Instructions 21-6 *44 RING DETECTION COUNT [00] | This field is only applicable if you are using a 4285/4286 VIP Module and/or if you willuse station-initiated downloading. Enter 00 to disable ring detection. Enter 01-14 for ring counts of 1-14. Enter 15 toselect Answering Mac...
Page 116 - *79 ZONE TYPE RESTORES FOR ZONE TYPES 1-8
Section 21 - Data Field Descriptions 21-7 option 3, fire alarms and supervisories go to the primary number only; all reports go tothe secondary number. *52 STANDARD/EXPANDED REPORT PRIMARY Alm Rst Byp Trbl Opn/Cls Low Batt Enter 0 for standard reporting or 1 for expanded reporting for the primary ph...
Page 117 - Set this field to 0 for UL installations.; . This account number can be the; *20 EXIT ERROR LOGIC
VISTA-100 Installation Instructions 21-8 *88 BURG. ALARM COMM. DELAY (partition-specific) [0] Enter 0 if you want no delay on burglary alarm communication. Enter 1 if you want a16-second delay (there is no delay on 24-hour zone-type alarms). Set this field to 0 for UL installations. *89 RESTORE REPO...
Page 118 - You must set this field to 000,000 for UL Burglary Installations.
Section 21 - Data Field Descriptions 21-9 1*23 CROSS ZONING PAIR TWO | | | | Enter the second pair of zones that must both be faulted within a 5-minute period tocause an alarm. Enter 000,000 to disable this feature, if you do not want to define asecond pair of cross-zones. You must set this field to...
Page 119 - *42 CALL WAITING DEFEAT
VISTA-100 Installation Instructions 21-10 1*33 TOUCHTONE W/ROTARY BACKUP [0] Enter 1 to enable rotary backup dialing if the communicator is not successful in dialingusing TouchTone DTMF on the first attempt. Enter 0 if you do not want this option. 1*34 COMM. SPLIT REPORT SELECTION [0] This field all...
Page 120 - *53 DISABLE DOWNLOAD CALLBACK; *73 PRINTER BAUD RATE
Section 21 - Data Field Descriptions 21-11 1*53 DISABLE DOWNLOAD CALLBACK [0] Enter 1 to disable the callback requirement for downloading. Enter 0 to require acallback. You must set this field to 0 for Commercial Fire and UL Commercial Burglaryinstallations. 1*56 50/60 Hz CLOCK SPEED [0] Enter 1 for...
Page 121 - *00 NUMBER OF PARTITIONS; You must set fields 2*05 through 2*08 to 0 for UL installations.
VISTA-100 Installation Instructions 21-12 command "57." (Refer to Section 22: #93 Menu Mode Programming and “Programmingwith #80 Scheduling Menu Mode” in Section 23: Scheduling Options.) 1*76 ACCESS CONTROL RELAY (partition-specific) [00] | You can program the system to provide user-activate...
Page 122 - *11 ALLOW DISARM OUTSIDE WINDOW IF ALARM OCCURS; Used this field only if field 2; *19 USE PARTITION DESCRIPTORS
Section 21 - Data Field Descriptions 21-13 suppressed during the closing window in order to prevent false alarms if the user armsthe system, then re-enters the premises (for example, to retrieve a forgotten item).Note that openings and closings are still recorded in the event log. Enter 0 if you do ...
Page 123 - Enter 1 to enable zone 6 as a tamper zone.; This option allows the delay time programmed in field 3
VISTA-100 Installation Instructions 21-14 2*24 DISPLAY TROUBLES OF OTHER PARTITIONS [0] Enter 1 if you want troubles that occur on other partitions to be displayed at thispartition's keypad(s). Enter 0 if you do not want such a display. 3*00 DISPLAY TRBL INSTEAD OF CHECK [0] Enter 1 if you want the ...
Page 124 - Enter 1 to enable each dialer that exists in the system.
Section 21 - Data Field Descriptions 21-15 3*21 MAX # OF DIALER RETRIES [8] Enter a number from 1 to 8 to set the maximum number of retries to each telephonenumber. You must enter 3, 4, or 5 for NFPA72-compliant systems if you program asecondary number. 3*30 DIALER SELECTION [0,0] Main Backup Enter ...
Page 125 - *61 AUX RELAY FUNCTION
VISTA-100 Installation Instructions 21-16 3*60 BELL 2 & AUX RELAY TIMEOUT [00,00] | | Bell 2 Aux. Rly. Use this field to define the length of time Bell Output 2 and the aux. relay will soundfor all audible alarms. The system will multiply the number you enter by 2 minutes tocalculate the actual ...
Page 126 - S E C T I O N 2 2; polling loop devices (all other zone characteristics must be
22-1 S E C T I O N 2 2 #93 Menu Mode Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ #93 Main Menu Options ♦ Zone Programming ♦ Storing Serial Numbers ♦ Report Code Programming ♦ Programming Alpha Descriptors ♦ Device Prog...
Page 128 - Zone Programming; 7 will not delete the tool’s serial
Section 22 - #93 Menu Mode Programming 22-3 #93 Menu Mode Key Commands #93 Enters Menu Mode. ✴ Serves as ENTER key. Press to have keypad accept the entry. [#] Backs up to the previous screen. 0 Press to answer NO and continue to the next menu. 1 Press to answer YES. 00 Escapes from Menu Mode and ret...
Page 132 - Enrolling Serial Numbers in Sequential Mode
Section 22 - #93 Menu Mode Programming 22-7 010 INPUT S/N A022-4064 The system will enroll the serial number of the first deviceheard and will display the number. If the serial and loop number combination is already present in the system, the keypad will sounda single long beep and display the word ...
Page 133 - 7 will not delete the tool’s serial number.); A loop number programmed
VISTA-100 Installation Instructions 22-8 To enroll serial numbers in Sequential Mode, take the following steps:1. Enter Data Field Programming Mode by entering [Installer Code] + 8 0 0 0. 2. From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. 3. Press 0 (NO) repea...
Page 135 - Report Code Programming; ALARM CODES; Zone Alarm Reports
VISTA-100 Installation Instructions 22-10 At any time during this step, you may press ✴ on the keypad or the upper left button of the program tool if you are satisfied with the serial and loop number combination that you haveenrolled, regardless of whether or not the enrolled input has been "con...
Page 137 - System Group 1 Codes
VISTA-100 Installation Instructions 22-12 double-digit entry) and press ✴ . The second digit will be the ID (second) digit of the Alarm report code for each zone (if programmed). Press ✴ to continue. ENTER ZN FOR GRP000 = QUIT 017 Enter one zone for each group of 16 zones. When you arefinished enter...
Page 138 - Programming Alpha Descriptors
Section 22 - #93 Menu Mode Programming 22-13 enter other system report codes, enter 0 (NO) and press ✴ to continue. System Group 3 Codes SYSTEM GROUP #3?1 = YES 0 = NO 0 To enter System Group #3 codes, press 1 (YES). EARLY OPEN1st 00 2nd 00 Enter the first digit of the Early Opening report code. Pre...
Page 139 - Zone Descriptors
VISTA-100 Installation Instructions 22-14 • Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words stored in memory, and any word can have an "s" or " ‘s"added to it. NOTE: Because the top line of the display contains the...
Page 140 - Custom Words
Section 22 - #93 Menu Mode Programming 22-15 Find the descriptor words you want to use in the fixed-word vocabulary list later in thissection. In this example, the description for zone 1 is “Back Door.” To enter thedescriptor, use one of the following two methods: • Press [#] followed by the 3-digit...
Page 141 - Partition Descriptors
VISTA-100 Installation Instructions 22-2 a. Press [#], followed by the 2-digit code that represents the first letter you would like todisplay (e.g., 65 for "A"), according to the ASCII chart later in this section.When the desired character appears, press 6 to select it. The cursor will move ...
Page 142 - Store the new display message in memory by pressing 8.; The system will ask for the next partition number.; Enter 0 to quit or 1-8 to enter a new partition number.
Section 22 - #93 Menu Mode Programming 22-3 A cursor will be present at the extreme left of the first line (over the first asterisk). Press6 to move the cursor to the right, or 4 to move the cursor to the left. You can press 7 toinsert spaces or erase existing characters. 2. Create the message. For ...
Page 143 - ALPHA DESCRIPTOR VOCABULARY
VISTA-100 Installation Instructions 22-4 ALPHA DESCRIPTOR VOCABULARY Use this vocabulary list to enter alpha descriptors. To select a word, press [#] followed by the word's 3-digit number.NOTE: This vocabulary is not to be used for relay voice descriptors. See “Relay Voice Descriptors” in thissectio...
Page 144 - Device Programming
Section 22 - #93 Menu Mode Programming 22-5 Device Programming Use this menu to program keypads, receivers, and relay modules. From Data Field Programming Mode, press #93 to display "ZONE PROG?". Press 0repeatedly to until "DEVICE PROG?" is displayed. DEVICE PROG?1=YES 0=NO Press 1 t...
Page 145 - Relay Programming
VISTA-100 Installation Instructions 22-6 SOUND OPTION If you entered device type 1 (alpha keypad), this prompt willappear. You can program keypads individually to suppressarm/disarm beeps, entry/exit beeps, and Chime mode beeps.This helps prevent unwanted sounds from disturbing users. Enter a number...
Page 147 - Programming Relay Output Devices
VISTA-100 Installation Instructions 22-8 B) 1. ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a RESTORE ZONE LIST, you can select a specific zone (response)type or system operation action to de-activate the device. If you choose a specific ZONE TYPE, when any zone of thatresponse type restores fr...
Page 148 - Type/System Operation table above. Press; specific group number. Press
Section 22 - #93 Menu Mode Programming 22-9 02 START: ZN TYPE You can use a Zone Type/System Operation instead of or inaddition to an Event/Zone List combination to start the relayaction. If you use a Zone Type/System Operation, enter one of the 2-digit codes listed below. Press ✴ to continue. Choic...
Page 149 - Zone List Programming
VISTA-100 Installation Instructions 22-10 01 FIRE BELL?1 = YES 0 = NO If this relay is on a supervised 4204CF module, you can use itas an additional fire bell. Enter 1 (YES) if it is to be used thisway; enter 0 (NO) if it is not. This tells the system whichrelays are to be activated during a fire dr...
Page 150 - Relay Voice Descriptors
Section 22 - #93 Menu Mode Programming 22-11 001 Zn to Delete?000=QUIT 000 Enter each zone number to be deleted from the Zone List, pressing ✴ after each number. View Zn LIST00=QUIT 00 To view a Zone List, press 00 at the “ENTER ZONE LIST”prompt. You will see the prompt at left. Enter the Zone List ...
Page 151 - Relay Voice Descriptors and Custom Word Substitutes Vocabulary; Custom Word Substitutes for VIP Module Annunciation; To enter custom word substitutes, take the following steps:; Enter 1 at this prompt.
VISTA-100 Installation Instructions 22-12 Relay Voice Descriptors and Custom Word Substitutes Vocabulary Word IndexAir ................... 116Alarm .............. 255And.................. 067Apartment....... 117Appliances....... 161Area................. 118Attic ................ 119 Baby ..............
Page 152 - to accept the entry.; RF Serial Number Clear Mode; The RF Serial Number Clear mode will; not delete polling loop serial numbers.; To clear all RF wireless serial numbers, take the following steps:
Section 22 - #93 Menu Mode Programming 22-13 01 ENTER INDEX # Enter the 3-digit substitute word index number from the RelayVoice Descriptors and Custom Word Substitutes Vocabulary List. Press ✴ to accept the entry. The system displays the "CUSTOM WORD NO." prompt.Enter the next custom word n...
Page 153 - S E C T I O N 2 3; Scheduling Options; Auto-disarming is not for use in UL installations.
23-1 S E C T I O N 2 3 Scheduling Options • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Introduction to Scheduling ♦ Time Window Definitions ♦ Open/Close Definitions ♦ Programming with #80 Scheduling Menu Mode ♦ Basic Scheduling Men...
Page 155 - Section 23 - Scheduling Options; Time Windows Definitions; Window
Section 23 - Scheduling Options 23-3 Time-DrivenEvents By using time windows, the system can automatically activate and de-activate relays at predetermined times to turn lights or other deviceson and off.The system can perform the same actions on a daily basis, or can bemade to perform an action onl...
Page 157 - Open/Close Definitions; Daily Schedule; Example of Open/Close Exception Reporting & Scheduling
Section 23 - Scheduling Options 23-5 Open/Close Definitions Opening and closing windows are controlled by schedules that you define. There are threetypes of schedule: Daily, Holiday, and Temporary. You can also use time-driven events toschedule opening and closing windows. Daily Schedule Each partit...
Page 158 - Programming with #80 Scheduling Menu Mode; Steps to Programming Scheduling Options; Basic Scheduling Menu Structure
VISTA-100 Installation Instructions 23-6 Programming with #80 Scheduling Menu Mode You can use #80 Scheduling Menu Mode to program most of the scheduling and timed-eventoptions. You can program other options through Data Field Programming Mode. To enter #80 Scheduling Menu Mode, the system must be i...
Page 160 - Time Windows Definitions Worksheet; Programming Time Windows; You cannot enter Scheduling Mode if any partition is armed.
VISTA-100 Installation Instructions 23-8 Time Windows Definitions Worksheet The system provides 20 time windows that you can define with start and stop times. Thesewindows are the basis of the scheduling system. You can use them for various open/closeand access schedules, as well as for output contr...
Page 161 - Daily Open/Close Worksheet
Section 23 - Scheduling Options 23-9 Time Window programming and display the “Quit?” prompt. Enter 0 at the “Quit?” prompt toreturn to the main menu choicesand continue programming. Enter 1to quit Scheduling Menu Mode. Quit?1 = YES 0 = NO 0 01 TIME WINDOW00:00AM 00:00AM If you entered a time window ...
Page 163 - Holiday Definitions & Schedule Worksheet; Programming Holiday Schedules
Section 23 - Scheduling Options 23-11 Holiday Definitions & Schedule Worksheet You can define up to 16 holidays for the system. Each holiday can be assigned to anycombination of partitions. List the desired holidays on the following worksheet. Check thepartitions to which each holiday applies. H...
Page 164 - Time-Driven Event Worksheet; To fill out the worksheet, take the following steps:
VISTA-100 Installation Instructions 23-12 When you have programmed all holidays, enter 00 at the“HOLIDAY NUMBER?” prompt to exit the Holiday menus. Time-Driven Event Worksheet You can program up to 20 events to be activated according to a time schedule. Each event isgoverned by previously defined ti...
Page 165 - Relay commands
Section 23 - Scheduling Options 23-13 Relay commands Action Code Action Specifier 01 Relay On Relay # 02 Relay Off Relay # 03 Relay Close for 2 seconds Relay # 04 Relay Close XX minutes (set in field 1*74) Relay # 05 Relay Close YY seconds (set in field 1*75) Relay # 06 Relay Group On Relay Group # ...
Page 166 - Action Code; Time-Driven Event Programming
VISTA-100 Installation Instructions 23-14 Open/Close Windows Activation time 3 (During) is the only valid choice for these functions: Action Code Action Specifier 40 Enable Opening Window by partition Partition(s) 41 Enable Closing Window by partition Partition(s) 42 Enable Access Window for Access ...
Page 168 - : Trigger at both the start and the end of the window.; Limitation of Access by Time Worksheet
VISTA-100 Installation Instructions 23-16 time that has been stored for the window is displayed. Press the ✴ to continue. 01 Active time? 0 Enter the activation code number (1, 2, 3, or 4) listed below. Asyou key in the number, the activation time is displayed. Thechoices are: 1: Trigger at the star...
Page 169 - #81 Temporary Schedule Menu Mode
Section 23 - Scheduling Options 23-17 Access Sched. ?1 Yes 0 = No 0 Enter 1 to program access schedules.If no limitations apply, enter 0. ACCESS SCHED # ?01-08, 00 = Quit 01 Enter the number of the access control schedule (01-08) you want to program. Press ✴ to accept the entry. When you are finishe...
Page 171 - Programming Temporary Schedules
Section 23 - Scheduling Options 23-19 Programming Temporary Schedules Only users with an authority level of manager or higher can program temporary schedules.A temporary schedule only affects the partition from which it is entered. Temporary schedules can be reused at later dates by pressing [#] to ...
Page 172 - #83 User Scheduling Menu Mode
VISTA-100 Installation Instructions 23-20 #83 User Scheduling Menu Mode The system provides up to 20 "timers" that allow the end user to control output devices(4204 relay). These timers are comparable to the individual appliance timers that can bepurchased at a department store. The output d...
Page 173 - Enter 0 to put the schedule in effect for one week only.
Section 23 - Scheduling Options 23-21 Enter 0 to put the schedule in effect for one week only. Press ✴ to accept the entry. The system will quit User Scheduling mode and return to normal mode.
Page 174 - S E C T I O N 24; System Communication; A Successful Transmission
24-1 S E C T I O N 24 System Communication • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ A Successful Transmission ♦ Reporting Formats ♦ Loading Communication Defaults • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • ...
Page 176 - Section 24 - System Communications; ADEMCO High Speed Reporting events by channel:; Channels 1 through 8 could have one of the following conditions:
Section 24 - System Communications 24-3 ADEMCO Contact ID Reporting takes the following format: CCCC QEEE GG ZZZwhere:CCCC = Customer (subscriber) ID Q = Event qualifier, where: E = new event and R = restore event EEE = Event code (3 hexadecimal digits) GG = Partition Number (system messages show 00...
Page 177 - Loading Communication Defaults; TABLE OF DEFAULT PROGRAMMING COMMANDS; • Assigns the following report codes:
VISTA-100 Installation Instructions 24-4 1234 5155 1555 1 (Acct #1234, with alarms on channels 9 and 12) LIMITATIONS • ADEMCO High Speed reporting provides 15 zone channels. If more than 15 zones are being used, theywill have to share channels. • With ADEMCO High Speed reporting, channels 9-15 canno...
Page 178 - TABLE OF CONTACT ID EVENT CODES
Section 24 - System Communications 24-5 TABLE OF CONTACT ID EVENT CODES Code Definition 110 Fire Alarm 111 Smoke Alarm* 113 Water Flow Alarm 121 Duress 122 Silent Panic 123 Audible Panic 131 Perimeter Burglary 132 Interior Burglary 133 24-Hour Burglary 134 Entry/Exit Burglary 135 Day/Night Burglary ...
Page 180 - COMMUNICATION DEFAULTS FOR ZONES
Section 24 - System Communications 24-7 COMMUNICATION DEFAULTS FOR ZONES Zone # Low Speed 1st 2nd Express 1st 2nd High Speed 1st 2nd Contact ID 1st 2nd 001 01 00 10 01 01 00 01 00 002 01 00 10 02 01 00 02 00 003 03 00 10 03 02 00 03 00 004 03 00 10 04 02 00 04 00 005 03 00 10 05 02 00 05 00 006 03 0...
Page 181 - COMMUNICATION DEFAULTS FOR ZONES (cont’d)
VISTA-100 Installation Instructions 24-8 COMMUNICATION DEFAULTS FOR ZONES (cont’d) Zone # Low Speed 1st 2nd Express 1st 2nd High Speed 1st 2nd Contact ID 1st 2nd 051 01 00 05 01 01 00 06 00 052 01 00 05 02 01 00 07 00 053 01 00 05 03 01 00 08 00 054 01 00 05 04 01 00 09 00 055 01 00 05 05 01 00 10 0...
Page 182 - TROUBLE
Section 24 - System Communications 24-9 COMMUNICATION DEFAULTS FOR ZONES (cont’d) Zone # Low Speed 1st 2nd Express 1st 2nd High Speed 1st 2nd Contact ID 1st 2nd 614 00 00 00 00 00 00 00 00 615 00 00 00 00 00 00 00 00 616 00 00 00 00 00 00 00 00 800 00 00 00 00 00 00 00 00 801 00 00 00 00 00 00 00 00...
Page 183 - BYPASS
VISTA-100 Installation Instructions 24-10 COMMUNICATION DEFAULTS FOR ZONES (cont’d) Zone # Low Speed 1st 2nd Express 1st 2nd High Speed 1st 2nd Contact ID 1st 2nd BYPASS 00 00 00 00 00 00 00 00 BYPASSRST. 00 00 00 00 00 00 00 00 DURESS 02 00 13 13 01 00 11 00 To program report codes, see “Report Cod...
Page 184 - S E C T I O N 25; Downloading Primer; (Remote Downloading is not a UL Listed feature); OR; Getting On-Line with a Control Panel
25-1 S E C T I O N 25 Downloading Primer (Remote Downloading is not a UL Listed feature) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ Getting On-Line with a Control Panel ♦ On-Line Control Functions ♦ Access S...
Page 185 - On-Line Control Functions
VISTA-100 Installation Instructions 25-2 2. Enter [Installer code] + [#] + 5. The panel temporarily enables a ring count of 5 and sets the Download Callback option to 1 (callback not required). 3. Call the panel using the downloader software set to First Communication Mode. 4. The downloader will es...
Page 186 - Section 25 - Downloading Primer; Access Security; the pre-programmed number only if the security codes match.; Connecting a 4100SM Module for Direct-Wire Downloading
Section 25 - Downloading Primer 25-3 • Set the real-time clock. Access Security Access to the control panel from a remote location is protected against compromise by 4levels of protection: 1. Security Code Handshake: The subscriber's account number as well as an 8-digit ID number (known only to the ...
Page 188 - S E C T I O N 26; Setting The Real-Time Clock
26-1 S E C T I O N 26 Setting The Real-Time Clock • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ Setting the Time and Date • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • ...
Page 190 - S E C T I O N 27; User Access Codes; To; You must program User #002 for the Quick Arm feature to function.; User Codes and Levels of Authority; Level Title
27-1 S E C T I O N 27 User Access Codes • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ User Codes and Levels of Authority ♦ To Add a Master, Manager, or Operator Code ♦ To Change a Master, Manager, or Operator C...
Page 191 - Level 1: Master Codes
VISTA-100 Installation Instructions 27-2 Level 0: Installer (User 1) • Program this level in field *00 (default = 5-1-4-0). Select installer Open/Close reporting in field *39. • A user with this level of authority can perform all system functions (arm, disarm, bypass, etc.), but cannot disarm the sy...
Page 192 - Level 6: Duress Codes; that to which he is assigned.
VISTA-100 Installation Instructions 27-2 • Operator C (sometimes known as the Babysitter code) cannot disarm the system unless the system was armed with that code. This code is usually assigned to persons who needto arm and disarm the system only at specific times (for example, a babysitter needs to...
Page 193 - Section 27 - User Access Codes; Multiple Partition Access Examples; To ADD a Master, Manager, or Operator Code
Section 27 - User Access Codes 27-3 Note that Open/Close reporting of Quick Arm is enabled if User 002 is enabled forOpen/Close reporting, and that Quick Arm reports as User 000. In order for Quick Armreports to be sent for all partitions, User 002 must have authority and Open/Close must beenabled f...
Page 195 - ) indicates the partition; To CHANGE a Master, Manager, or Operator Code; To exit User Edit Mode, take ONE of the following steps:
Section 27 - User Access Codes 27-5 global arm options that you programmed for each partition towhich you granted the user access. For example: Part. 1 A0 ✴ WHSE User 003 Auth=3G. Note that the “G” following the authority level indicates thatthe global arm feature is enabled for this user in the dis...
Page 196 - S E C T I O N 28; Keypad Functions
28-1 S E C T I O N 28 Keypad Functions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Information ♦ Arming Functions ♦ Global Arming ♦ Access Control ♦ Delaying Closing Time ♦ Partition "GOTO" Command ♦ Viewing Capabi...
Page 197 - Global Arming
VISTA-100 Installation Instructions 28-2 SYSTEM COMMANDS FUNCTION ACTION Display FaultedZones Before arming, the system must be in the READY condition (all zones mustbe intact). If the "NOT READY" message appears, press the READY key todisplay faulted zones. Arming Away Enter code + 2 (AWAY)...
Page 198 - Section 28 - Keypad Functions; Viewing Capabilities of a User
Section 28 - Keypad Functions 28-3 • If, when you are disarming the system using a Global Disarm, any of the selected partitions has a condition that would cause the keypad to beep (such as alarm memoryor a trouble condition), the keypad will beep and enter a summary mode in which thealarm memory or...
Page 199 - Viewing Zone Descriptors; The panic functions are identified by the system as follows:
VISTA-100 Installation Instructions 28-4 Part. 1 A0T WHSE User 01 Auth.=1G. The user's Open/Close report capability is shown by the periodfollowing the authority level. If Open/Close is not enabled for auser, the period will not appear. Viewing Zone Descriptors Alpha keypads can display all programm...
Page 200 - Desired function; ENTER USER CODE
Section 28 - Keypad Functions 28-5 • Arming sequences that involve bypassing certain zones before arming.• Seldom-used but repeatable sequences.• Relay activation sequences. To program a macro, enter your user code + [#] + [D]. The following prompt appears: ENTER SPEED KEY"D" [ ] (If there i...
Page 201 - On the keypad, press
VISTA-100 Installation Instructions 28-6 nn DEVICE IS OFF HIT 0=OFF , 1=ON Voice: "[voice descriptor] DEVICE nn ON/OFF. FOR [voicedescriptor] ON ENTER 1, FOR [voice descriptor] OFF ENTER0" Press 0 or 1 to turn the device off or on, respectively.NOTE: "nn" represents the 2-digit relay...
Page 202 - S E C T I O N 29; Testing The System; If the following is displayed,; press
29-1 S E C T I O N 29 Testing The System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Checkout Procedure for Hardwired Zones ♦ Checkout Procedure for Polling Loop Zones ♦ Checkout Procedure for Wireless Zones ♦ Battery Test ♦ Diale...
Page 203 - Checkout Procedure for Polling Loop Zones; system should display:; press the
VISTA-100 Installation Instructions 29-2 to which the zone is assigned should display the number of the faulted zone. Trippingfire and panic zones will cause external sounders to sound, and may trigger thedialer. When each zone is restored, the “READY TO ARM” message should appearagain. If one or mo...
Page 204 - The 4278 auxiliary sensor loop cannot be used.; Checkout Procedure for Wireless Zones; Transmitter ID Sniffer Mode; wireless units programmed into the system.
Section 29 - Testing The System 29-3 5. When you see the proper display on the keypad(s), the polling loop zones in the system are functioning properly. 6. Power-down and continue the testing procedure. UL • The 4208 must be mounted either inside the VISTA-100 cabinet or in a separate enclosurethat ...
Page 205 - Battery Test
VISTA-100 Installation Instructions 29-4 • If you are using a single receiver, the keypad will beep three times to indicate that it has received a signal. If you are using two receivers, the keypad will beep once if thefirst receiver received the signal, twice if the second receiver received the sig...
Page 207 - Armed Burglary System Test; To conduct an Armed Burglary System Test, take the following steps:
VISTA-100 Installation Instructions 29-6 Burglary Walk-Test (Code + TEST 5) The Burglary Walk-Test causes the system to sound keypad beeps in response to faults onburglary and non-fire related 24-hour zones for the purpose of allowing proper zoneoperation to be checked without triggering alarms. Not...
Page 208 - Section 29 - Testing The System; Trouble Conditions; Supervisory Messages; A polling loop zone is not detected by the control panel.; Other System Messages; Indicates that the control is on-line with a remote computer.; Fire System Off-Normal Report
Section 29 - Testing The System 29-7 Trouble Conditions Supervisory Messages A keypad display of “SUPV” accompanied by a zone number (001-087) and an alpha descriptor (if one has been programmed) indicates that a fire supervisory condition exists on thatzone. This means that the operation of the fir...
Page 209 - Power Failure; Turning the System Over to the User
VISTA-100 Installation Instructions 29-8 • Fire trouble on any zone (zone response types 9, 16, 17, 18, 19)• Fire supervisory present (zone response type 18)• Unrestored fire alarm on any zone• Bypass of any fire zone• Bell circuit fault for any supervised fire bell• Bypass/disable of any supervised...
Page 210 - Contacting Technical Support; along with any documentation that came with the product.
Section 29 - Testing The System 29-9 Contacting Technical Support PLEASE! Before you call Technical Support, be sure you: • READ THE INSTRUCTIONS!• Check all wiring connections.• Determine that the power supply and/or backup battery are supplying proper voltages.• Verify your programming information...
Page 212 - A P P E N D I X A; Regulatory Agency Statements; UL Installation Requirements; All partitions must be owned and managed by the same person(s).; UL864/NFPA Local Fire
Appendix A-1 A P P E N D I X A Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • UL Installation Requirements The following requirements apply to both UL Residential and UL Commercial Burglaryinstallations: • All partitions m...
Page 213 - UL365 Police Station Connected Burglar Alarm; Follow the instructions below for UL609 local installations.; For Grade AA Service:; You must use a 7920SE Long Range Radio.
VISTA-100 Installation Instructions Appendix A-2 • If a secondary number is programmed, set the maximum number of dialer re-tries to 3, 4, or 5 in field 3*21. UL609 Grade A Local Mercantile Premises/Local Mercantile Safe & Vault • All zones must be configured for EOLR supervision (field *41=0). ...
Page 214 - Appendix A - Regulatory Agency Statements; California State Fire Marshal (CSFM) Requirements
Appendix A - Regulatory Agency Statements Appendix A-3 For Grade AA Service: • Follow the instructions for Grade A service, except use the 7920SE in place of the 7720. California State Fire Marshal (CSFM) Requirements For 24-hour battery back-up: The California State Fire Marshal has published new r...
Page 218 - A P P E N D I X B; DIP Switch Tables
Appendix B-1 A P P E N D I X B DIP Switch Tables • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
Page 220 - Appendix B - DIP Switch Tables; DIP SWITCH TABLES FOR POLLING LOOP DEVICES
Appendix B - DIP Switch Tables Appendix B-3 DIP SWITCH TABLES FOR POLLING LOOP DEVICES 4275 PIR MIRROR DIP SHOWN SET FOR ID 10 (A) SIDE VIEW (UP) 1 2 3 4 5 6 7 UP DN POS. 6: UP (A), DN (B) = INST. MODE DN (A), UP (B) = PULSE COUNT POS. 7: UP (A), DN (B) = WALK TEST DN (A), UP (B) = W/T DISABLE } 419...
Page 221 - DIP SWITCH TABLES FOR 5700 RF SYSTEM WIRELESS DEVICES
VISTA-100 Installation Instructions Appendix B-4 DIP SWITCH TABLES FOR 5700 RF SYSTEM WIRELESS DEVICES HOUSE ID (1 SHOWN) HOUSE ID (1 SHOWN) HOUSE ID (1 SHOWN) 1 2 3 4 5 6 UP DN 1 2 3 4 5 UP DN 1 2 3 4 5 6 7 8 UP DN 1 2 3 4 5 6 7 8 9 10 UP DN 5706/5707 SMOKE DETECTOR/TRANSMITTER 5775 PIR DETECTOR/TR...
Page 222 - A P P E N D I X C; Summary of System Commands
Appendix C-1 A P P E N D I X C Summary of System Commands • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Event Logging Commands Event Log Display = Code + [#] + 60 (Installer or Master only)Event Log Print = Code + [#] + 61 (Installer or Master only)C...
Page 223 - Scheduling
VISTA-100 Installation Instructions Appendix C-2 Scheduling Commands Installer-Programmed Schedule Events = Installer Code + [#] + 80Temporary Schedule Editing = User Code + [#] + 81 (Installer, Master, Manager only) Extend Closing Window = User Code + [#] + 82 (Installer, Master, Manager only) End ...
Page 224 - A P P E N D I X D; Specifications; 140DLM BACKUP DIALER MODULE
Appendix D-1 A P P E N D I X D Specifications • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • VISTA-100 CONTROL Physical: 18”H X 14.5”W X 4.3”D Electrical: Primary Power: From ADEMCO No. 1451 Transformer with enclosure; rated 18VAC, 72VA Backup Battery...
Page 225 - DIGITAL COMMUNICATOR
VISTA-100 Installation Instructions Appendix D-2 DIGITAL COMMUNICATOR Formats Supported: ADEMCO High SpeedADEMCO 4+2 ExpressADEMCO Low SpeedADEMCO Contact IDSescoaRadionics Low Speed Line Seize: Double Pole Ringer Equivalence: 0.7B FCC Registration No.: AC398U-68192-AL-E 6139(R) REMOTE KEYPAD Physic...
Page 226 - Index
Index-1 Index • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 1451 Enclosure, 4-41451 Transformer, 4-424-Hour Audible Alarm, 19-224-Hour Auxiliary Alarm, 19-224-Hour Silent Alarm, 19-24146 Keyswitch, 1-54285/4286 VIP Module, 10-15140DLM Backup Dialer, ...
Page 232 - ADEMCO LIMITED WARRANTY; Notes
ADEMCO LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiariesand affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its products to be inconformance with its own plans and specifications and to be free fro...