3M 7626-T-110 - Manual
3M 7626-T-110 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Kit Selection Table
- Page 3 – Instructions for Tape Shielded Cable; Prepare Cable; BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG.; Aluminum Lug; Install Ground Braid; SINGLE
- Page 4 – SINGLE WRAP
- Page 5 – Install Lug or Connector; DO NOT REMOVE CORE AT THIS TIME.
- Page 6 – Install Termination; Correct Installation of Termination on Tape Shielded Cable
- Page 7 – Instructions for Wire Shielded Cable; BE SURE TO ALLOW FOR DEPTH OF
- Page 8 – Install Ground Braid
- Page 10 – Install Lug or Connector; DO NOT ALLOW SOLVENT TO TOUCH SEMI-CON INSULATION SHIELD!; Install Termination
- Page 11 – Correct Installation of Termination on Wire Shielded Cable; Instructions for UniShield
- Page 13 – Install Ground Braid
- Page 14 – Install Lug or Connector; DO NOT REMOVE CORE AT THIS TIME
- Page 15 – Install Termination
- Page 17 – Tooling Index
- Page 20 – M MAKES NO OTHER WARRANTIES
3M
™
Cold Shrink QT-III Silicone Rubber Indoor
Tubular Termination Kit
With High-K Stress Relief
For Tape Shield, Wire Shield and UniShield
®
Cable
7622-T-110, 7623-T-110, 7624-T-110, 7625-T-110,
7626-T-110
Instructions
IEEE Std. No. 48
Class 1 Termination
15 kV Class
110 kV BIL
F
CAUTION
Working around energized systems may cause serious injury or death. Installation should
be performed by personnel familiar with good safety practice in handling electrical
equipment. De-energize and ground all electrical systems before installing product.
September 2014
78-8113-5099-6 Rev E
3
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 78-8113-5099-6 Rev E 1.0 Kit Contents 3 High–K, Tracking Resistant, Silicone Rubber Terminations3 Pre-formed Ground Braids3 Constant Force Springs3 3M ™ EMI Copper Foil Shielding Tape 1181 Strips, 1/2" x 10" 6 Strips Scotch ® Mastic Strip 2230 (black with white release liners, bagged) 1 3M...
78-8113-5099-6 Rev E 3 2.0 Instructions for Tape Shielded Cable Prepare Cable 2.1 Check to be sure cable size fits within kit range as shown in Table 1. 2.2 Prepare cable using dimensions shown in Figure 1. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG. If necessary to prevent tape shield from unrollin...
4 78-8113-5099-6 Rev E 3.2 Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. PLEASE NOTE: The ground braid needs to make full contact with the metallic tape shield. Position long tail of ground braid, extending over cable jacket with solder...