3M 7620-T-95 - Manual

3M 7620-T-95

3M 7620-T-95 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
Page: / 20

Table of Contents:

  • Page 2 – NOTE: Do Not use knives to open plastic bags.; Kit Selection Table; NOTE: Final Determination Factor is cable insulation diameter.; Kit Number; Table 1
  • Page 3 – Instructions For Tape Shielded Cable; Check to be sure cable size fits within kit range as shown in; Be Sure To allow for depTh of Terminal; EMI; Single wrap; Figure 1
  • Page 4 – Install Ground Braid; Figure 2; spring after wrapping the final winding.; Figure 3
  • Page 5 – Figure 4; Install Lug or Connector; Check to insure 3M; do noT remoVe Core; Figure 5; Connector and Lug crimping information.; do noT allow SolVenT To TouCh Semi-Con inSulaTion Shield!
  • Page 6 – Install Termination; Figure 6; Vinyl Tape Marker; Correct Installation of Termination on Tape Shielded Cable
  • Page 7 – Instructions for Wire Shielded Cable; Check to be sure cable size fits within kit range as shown in; Be Sure To allow for depTh of; Figure 7; Figure 8
  • Page 8 – Install Ground Braid; Figure 9
  • Page 9 – spring and exposed shield wires (
  • Page 10 – Install Lug or Connector; do noT remoVe Core aT ThiS Time.
  • Page 11 – Install Termination; vinyl tape marker previously applied (; Correct Installation of Termination on Wire Shielded Cable
  • Page 12 – Check to be sure cable size fits within kit range as shown in; ALUMINUM lugs or connectors.
  • Page 13 – Remove semi-conductive jacket to dimension shown in; Install Ground Braid; Select a Scotch
  • Page 14 – Single
  • Page 15 – Install Lug or Connector
  • Page 16 – Install Termination; Correct Installation of Termination on UniShield
  • Page 17 – Tooling Index
  • Page 18 – One hole
  • Page 19 – Stem Connectors
  • Page 20 – M MAKES NO OTHER WARRANTIES
Loading the manual

3M

Cold Shrink QT-III Silicone

Rubber Indoor Termination Kit

With High-K Stress Relief
For Tape Shielded, Wire Shielded and UniShield

®

Cable

7620-T-95
Instructions

IEEE Std. No. 48

Class 1 Termination

5/8 kV Class

95 kV BIL

F

CAUTION

Working around energized systems may cause serious injury or death. Installation should

be performed by personnel familiar with good safety practice in handling electrical

equipment. De-energize and ground all electrical systems before installing product.

March 2013

78-8113-5098-8 Rev F

3

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - NOTE: Do Not use knives to open plastic bags.; Kit Selection Table; NOTE: Final Determination Factor is cable insulation diameter.; Kit Number; Table 1

2 78-8113-5098-8 Rev F 1.0 Kit Contents 3 High–K, Tracking Resistant, Silicone Rubber Terminations3 Preformed Ground Braids3 Constant Force Springs3 3M ™ EMI Copper Foil Shielding Tape 1181 Strips, 1/2" x 10" 6 Strips Scotch ® Mastic Strip 2230 (black with white release liners, bagged) 1 3M ...

Page 3 - Instructions For Tape Shielded Cable; Check to be sure cable size fits within kit range as shown in; Be Sure To allow for depTh of Terminal; EMI; Single wrap; Figure 1

78-8113-5098-8 Rev F 3 Instructions For Tape Shielded Cable 2.0 Prepare Cable 2.1 Check to be sure cable size fits within kit range as shown in Table 1 . 2.2 Prepare cable using dimensions shown in Figure 1 . Be Sure To allow for depTh of Terminal lug. If necessary to prevent tape shield from unroll...

Page 4 - Install Ground Braid; Figure 2; spring after wrapping the final winding.; Figure 3

4 78-8113-5098-8 Rev F 3.0 Install Ground Braid 3.1 Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. PLEASE NOTE: The ground braid needs to make full contact with the metallic tape shield. Position long tail of ground braid, extending over...