Motor Lead Pigtail Splice

for 5/8 kV Non-Shielded Cables

for 1000 Volts or less cables (heavy-duty and two-hole lug applications)

Instructions

78-8096-4634-8-

F

Kit Contents (kit contains 3 splices):

3—Lug Covers

3—Locking Pins

3—Tubes Silicone Grease

3—Bag Solvent Cleaning Cloths

3—Mastic Sealing Strip(s)*

3— Strips Scotch

®

Linerless Rubber

Splicing Tape

130C

3—Instruction Sheet

*Quantity varies with kit number.

Kit

Cable

Size

Range

Cable

Max.

Number

(AWG/kcmil)

Insulation

Bolt

Feeder Motor

Lead O.D.

Range Length

5316

8–4

10–4

0.30–0.51

in.

1

2

in.

5317

2–1/0

4–1/0

0.43–0.65

in.

3

4

in.

5318

1/0–250

2–250

0.53–0.88

in.

1

1

4

in.

5319

250–500

4/0–500

0.75–1.12

in.

1

1

2

in.

3M

Motor Lead

Pigtail Splice Kits

for 5/8 kV or less Non-Shielded Cables

5316, 5317, 5318, 5319

Technical Information:

• For non-shielded cables

• Rated 5/8 kV

• For cables rated 1000 Volts or less (heavy-duty and two

hole lug applications)

• Cable Size Range: Feeder: #8 AWG—500 kcmil

Motor Lead: #10 AWG—500 kcmil

• Copper Conductors


CSA Certified for

600V or Less

Table 1

Caution

Working around energized systems may cause serious

injury or death. Installation should be performed by

personnel familiar with good safety practice in handling

electrical equipment. De-energize and ground all

electrical systems before installing product.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Figure 1; Prepare Cable According to Standard Procedures; fordepth of lug barrel.; Figure 2; Install Lug Cover; Separate cables and apply mastic strip between and around them,; Figure 3

2 78-8096-4634-8- F Scotch ® Linerless Rubber Splicing Tape 130C Figure 1 1.0 Prepare Cable According to Standard Procedures 1.1 Check to be sure cables fit within cable kit range as shown in Table 1 on cover.1.2 Remove cable insulation for length recommended by terminal lug manufacturer; if no info...

Page 3 - Figure 4; will aid in the installation of the Lug Cover.

78-8096-4634-8- F 3 Scotch ® Linerless Rubber Splicing Tape 130C Figure 4 Figure 5 3.3 FOR 8 kV ONLY. Cover the lugs and bolt with four half-lapped layers of Scotch ® Linerless Rubber Splicing Tape130C (Figure 4). Note:  Lug cover will be printed with 5 kV rating.  Mastic layer qualifies the part as...

Page 4 - Important Notice; regardless of the legal theory asserted.; Electrical Markets Division

4.0 Tooling Index Lug and Crimping Information for 3M ™ Scotchlok ™ Copper Lugs 30014 through 30045 31145 through 31166 One hole Two hole 5.0 Copper Lugs 3M ™ CRIMPING TOOL-DIE SETS (NUMBER OF CRIMPS) Cable Stud Scotchlok ™ Square D Co. Size Size Copper Lug Burndy Corporation Thomas & Betts Corp...

Other 3M Models

All 3M Other