3M 5317 - Manual
3M 5317 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Figure 1; Prepare Cable According to Standard Procedures; fordepth of lug barrel.; Figure 2; Install Lug Cover; Separate cables and apply mastic strip between and around them,; Figure 3
- Page 3 – Figure 4; will aid in the installation of the Lug Cover.
- Page 4 – Important Notice; regardless of the legal theory asserted.; Electrical Markets Division
Motor Lead Pigtail Splice
for 5/8 kV Non-Shielded Cables
for 1000 Volts or less cables (heavy-duty and two-hole lug applications)
Instructions
78-8096-4634-8-
F
Kit Contents (kit contains 3 splices):
3—Lug Covers
3—Locking Pins
3—Tubes Silicone Grease
3—Bag Solvent Cleaning Cloths
3—Mastic Sealing Strip(s)*
3— Strips Scotch
®
Linerless Rubber
Splicing Tape
130C
3—Instruction Sheet
*Quantity varies with kit number.
Kit
Cable
Size
Range
Cable
Max.
Number
(AWG/kcmil)
Insulation
Bolt
Feeder Motor
Lead O.D.
Range Length
5316
8–4
10–4
0.30–0.51
in.
1
⁄
2
in.
5317
2–1/0
4–1/0
0.43–0.65
in.
3
⁄
4
in.
5318
1/0–250
2–250
0.53–0.88
in.
1
1
⁄
4
in.
5319
250–500
4/0–500
0.75–1.12
in.
1
1
⁄
2
in.
3M
™
Motor Lead
Pigtail Splice Kits
for 5/8 kV or less Non-Shielded Cables
5316, 5317, 5318, 5319
Technical Information:
• For non-shielded cables
• Rated 5/8 kV
• For cables rated 1000 Volts or less (heavy-duty and two
hole lug applications)
• Cable Size Range: Feeder: #8 AWG—500 kcmil
Motor Lead: #10 AWG—500 kcmil
• Copper Conductors
CSA Certified for
600V or Less
Table 1
Caution
Working around energized systems may cause serious
injury or death. Installation should be performed by
personnel familiar with good safety practice in handling
electrical equipment. De-energize and ground all
electrical systems before installing product.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 78-8096-4634-8- F Scotch ® Linerless Rubber Splicing Tape 130C Figure 1 1.0 Prepare Cable According to Standard Procedures 1.1 Check to be sure cables fit within cable kit range as shown in Table 1 on cover.1.2 Remove cable insulation for length recommended by terminal lug manufacturer; if no info...
78-8096-4634-8- F 3 Scotch ® Linerless Rubber Splicing Tape 130C Figure 4 Figure 5 3.3 FOR 8 kV ONLY. Cover the lugs and bolt with four half-lapped layers of Scotch ® Linerless Rubber Splicing Tape130C (Figure 4). Note: Lug cover will be printed with 5 kV rating. Mastic layer qualifies the part as...
4.0 Tooling Index Lug and Crimping Information for 3M ™ Scotchlok ™ Copper Lugs 30014 through 30045 31145 through 31166 One hole Two hole 5.0 Copper Lugs 3M ™ CRIMPING TOOL-DIE SETS (NUMBER OF CRIMPS) Cable Stud Scotchlok ™ Square D Co. Size Size Copper Lug Burndy Corporation Thomas & Betts Corp...